1. Home
  2. Equipment
  3. Alarm and pressure sensors

Alarm Sensors, Pressure Sensors and Particle Counters

Temperature and humidity tell you what is happening to the product right now. These sensors tell you why, and let you step in before the temperature goes out of range: the power has failed, water is leaking, a cooling unit has stopped, or the pressure cascade in a cleanroom has been disrupted. All of them connect to the same monitoring system, are written to the same archive and raise alarms under the same rules as temperature.

Water leak, dry contact, 220 volt power presence and differential pressure sensors
Schematic illustrations of alarm and differential pressure sensors.

Water leak sensor

It trips when water bridges the contacts of the sensing element on the floor. It is installed where a leak would damage product or stop equipment first and would otherwise go unnoticed for a long time: under cooling units and evaporators, next to drain pans, in ventilation plant rooms, server and equipment rooms, and under the hydraulic assemblies of humidification systems.

The specific model, its number in the Federal Register of Approved Measuring Instruments and the verification interval are stated in the project specification and in the delivery passport.
Sensing elementremote sensing cable or a spot sensor on the floor
Sensing cable lengthup to several tens of meters, extendable in sections
Outputdry contact to a digital input, or a separate address on the RS-485 line
Response timea few seconds from the moment of contact
Powerfrom the monitoring system line, backed up by the cabinet UPS
Optionalcan control a motorized water shut-off valve

A leak under a cooling unit often means more than water on the floor: it may be the start of a failure, such as a clogged drain or an evaporator icing up. That is why it makes sense to route the leak signal not as a “cleaning” task but as a technical alarm with its own recipient.

Dry contact input

This is not a measuring instrument but a way to bring a ready-made signal from third-party equipment into the system: a cooling unit, an automation panel, the fire alarm, a UPS, a cold room door. Most industrial devices have an “alarm” or “running” relay output, and that is what gets connected.

What is connectedWhat the system showsWhy
cooling unit alarm relay“Cooling unit: alarm” with a timestampit is clear why the temperature started to drift
cold room door limit switchduration and number of door openingsexplains temperature spikes and keeps staff disciplined
compressor “running” relayoperating hours and number of startsearly detection of wear
UPS “on battery” outputswitchover to backup powertime to act before the batteries run down
fire alarm outputevent in the common loga single picture of the whole site
manual call button“staff call” eventrecords of abnormal situations
The specific model, its number in the Federal Register of Approved Measuring Instruments and the verification interval are stated in the project specification and in the delivery passport.
Input typedigital, normally open or normally closed, configurable
Number of inputs2 to 16 inputs per module, modules can be added
Galvanic isolationyes, so that a fault in a third-party panel cannot damage the system
Debounce filterconfigurable, to avoid spurious events
Behavioralarm on activation and on the duration of a state

220 V power presence sensor

It checks whether power is present on a specific phase or line: at the cold room supply, on the socket circuit feeding a medical refrigerator, in the distribution board of a frozen storage warehouse. The system will notice a general power outage anyway, because the sensors go silent, but a power presence sensor answers a more precise question: exactly where the power was lost and when it came back.

The specific model, its number in the Federal Register of Approved Measuring Instruments and the verification interval are stated in the project specification and in the delivery passport.
Monitored voltageAC 220 V (single-phase version) or 380 V (three-phase version)
Trip thresholdconfigurable, typically 150–180 V
Galvanic isolationmandatory: the power circuit is separated from the data line
Outputdry contact or an address on the RS-485 line
InstallationDIN rail in the distribution board, performed by a qualified electrician
Alarminstant, with the time of loss and restoration recorded

Important for the cold chain. A power loss is recorded as an event in its own right, not only as the temperature rise that follows. This is exactly what is asked when a deviation is investigated: when the power was lost, how long the outage lasted, what the temperature did during that time and who was notified.

Pressure sensors

Monitoring systems use two different instruments, and they should not be confused.

TypeWhat it measuresWhere it is usedTypical range
Differential pressure sensorthe pressure difference between two rooms, or upstream and downstream of a filtercleanrooms, airlocks, operating rooms, isolation boxes, isolators0…±100 Pa and 0…±250 Pa
Absolute pressure sensorbarometric pressure in the roomlaboratories, climatic chambers, test areas80…110 kPa
The specific model, its number in the Federal Register of Approved Measuring Instruments and the verification interval are stated in the project specification and in the delivery passport.
Accuracy (differential pressure)typically ±(1…2) % of the upper measurement limit
Connectiontwo impulse tubes through bulkhead fittings in the wall
OutputRS-485 Modbus RTU, analog 4–20 mA or 0–10 V
Displayversions with a display for installation in the room
Metrologymeasuring instrument of an approved type with valid verification
Role in the systemcontinuous recording of the value and an alarm if the cascade is disrupted

How a pressure cascade is designed and what the regulations require is covered in detail on the Cleanrooms page.

Particle counter

Portable particle counter with an isokinetic sampling probe and a display
Particle counter: the instrument determines the number of particles of 0.5 and 5 µm per cubic meter of air.

A particle counter is the measuring instrument used to confirm the air cleanliness class under GOST R ISO 14644-1-2017. It draws a known volume of air through an optical chamber and counts the particles, sorting them by size.

VersionHow it is usedWhen it is chosen
Portable counterqualification and periodic monitoring at sampling points, with results entered in the protocolroom classification, routine monitoring, deviation investigations
Fixed counter with continuous samplingcontinuous monitoring of a critical zone, with data sent to the monitoring systemGrade A and B zones, filling, aseptic assembly
Multi-point manifolda single counter polls several sampling points in sequenceseveral critical points on a limited budget
The specific model, its number in the Federal Register of Approved Measuring Instruments and the verification interval are stated in the project specification and in the delivery passport.
Particle sizesat least 0.5 and 5.0 µm, the sizes used to classify rooms
Flow ratetypically 28.3 L/min (1 ft³/min in non-Russian datasheets); the rated flow rate matters for classification
Sampling probeisokinetic probe facing into the airflow
Data outputdisplay, printed report, transfer to the monitoring system
Metrologyapproved type and valid verification; without them the result will not be accepted
Samplingthe sample volume and number of locations are calculated per GOST R ISO 14644-1-2017

How these sensors work together

  1. Event

    Power is lost at the cold room supply. The 220 V sensor records the moment.

  2. Alarm

    The system immediately notifies the person on duty: on screen, with a sound, in the mobile app and through the selected channels.

  3. Context

    The archive shows alongside it that the cooling unit raised an alarm, the cold room door was not opened and the temperature is still in range, so there is time to act.

  4. Decision

    Staff follow the procedure: backup power, moving the product, calling the service team.

  5. Review

    The report includes every event with timestamps and acknowledgements, which is enough to assess the deviation.

What we need to select the equipment

  • A list of zones and rooms with their storage conditions or cleanliness classes.
  • What needs to be monitored besides temperature: leaks, power, doors, cooling units, pressure, particles.
  • Whether the existing equipment has “alarm” and “running” relay outputs.
  • The power supply diagram: which supplies and circuits need to be monitored.
  • For cleanrooms: the pressure cascade diagram and a list of critical pressure differentials.

Frequently asked questions

How is a dry contact different from a sensor?

A sensor measures a quantity and transmits a number. A dry contact is simply closed or open: a way to receive a ready-made signal from third-party equipment. In the system it appears as a timestamped event rather than as a chart.

Do a leak sensor and a dry contact input require verification?

No. Verification applies to measuring instruments: temperature, humidity and pressure sensors, and particle counters. A leak sensor and a digital input do not measure anything, so they are not subject to verification. Only instruments whose readings you present during inspections are verified.

Can these sensors be added to a system that is already running?

Yes, if the cabinet has free inputs or room for an expansion module. They are a standard addition to a Hladverk Group system; third-party systems can take them if they support Modbus RTU.

What differential pressure is considered normal in a cleanroom?

The standard value between adjacent rooms of different grades is 10–15 Pa (EAEU Good Manufacturing Practice Rules, Annex 1). The specific values for your facility are set by the design and confirmed during qualification.

Should we buy a particle counter, or can one be brought in for qualification?

It depends on the task. For periodic classification it is usually enough to bring in a verified instrument together with a specialist. Owning a counter makes sense when monitoring is needed frequently or continuously in Grade A and B zones.

How many leak sensors does a cold room need?

The count is based not on floor area but on where water will run first: under the cooling unit, next to the drain, at the lowest point of the floor. A typical cold room needs one or two points, and the sensing cable is laid around the perimeter of the risk zone.

Send us a list of your zones and what needs monitoring besides temperature, and we will select the sensors and price the kit.

Request a quote

We will call you back

Pick a day and time (Moscow time) and our manager will call you.

When to call